A-A-50782
4. Work surface |
Melamine resin equal to Formica or Micarta (registered trademarks). Color blue, light gray, frost green or white. |
5. Lighting |
- 150 foot candles min. at work surface, color whites fluorescent type, self-contained Underwriter Laboratories (U.L.) approved. |
6. Prefilters |
- Throwaway replacement type, removable from front. |
7. Final filters |
- HEPA (High Efficiency Particulate Air) 99.99% or more effective on particles 0.3 micron and larger 100% leak probed. Aluminum separators removable from bear. |
8. Filter mounting |
- Spring tension compression seal. |
9. Blower |
- Direct drive type. To maintain minimum average 90 cubic feet per minute. Variably controlled. |
10. Blower control |
- Solid state. Mounted in blower housing. |
11. Electrical |
- 115v/60 Hz, single phase, shall meet NFPA 70. All components shall be U.L. approved. |
12. Power cord |
- Six foot three wire power cord of adequate size to operate fan motors and lights shall exit from back of cabinet. Termination shall be standard, three prong plug. |
13. Motor |
- Shall meet NEMA Standard MG-1. |
14. Work area |
- Minimum 46.5 inches wide by 22 inches deep by 22 inches high. Work surface 30 to 32 inches from floor. |
15. Performance |
- Dust count: Less than 100 particles/cu ft 0.3 micron and larger shall meet class 100 “Clean Work Station” requirements of Federal Standard 209 and Air Force T.O. 00-25-203. |
16. Overall size and weight |
- 60 inches high X 34 inches deep X 51 inches wide - 450 lbs, (for reference only). |
Workmanship. Clean Work Stations shall be clean and free from faulty construction or any defect which affects appearance, serviceability, and durability.
For Parts Inquires submit RFQ to Parts Hangar, Inc.
© Copyright 2015 Integrated Publishing, Inc.
A Service Disabled Veteran Owned Small Business